Retrofit power module

  • Bildtitel

    Untertitel hier einfügen
    Button
  • Bildtitel

    Untertitel hier einfügen
    Button
  • Bildtitel

    Untertitel hier einfügen
    Button
  • Bildtitel

    Untertitel hier einfügen
    Button

Intended for installation in the control cabinet front


This saves you valuable space on the mounting plate and valuable wiring time with our prefabricated compact power modules


LM4i, 4-fach Triacmodul

The 4-channel power module is for switching AC voltages on resistive loads, zero-voltage switching up to 16A per channel. It is intended for installation in the control cabinet front. The external heat sink ensures the necessary heat dissipation and a seal guarantees protection class IP54. The triacs are protected by integrated, super-fast fuses that are accessible from the inside, which eliminates additional installation and wiring work. The mains voltage can be supplied separately per channel or to several channels via optional bridges, which enables individual phase distribution. The outputs are connected via 6.3mm flat connectors. All inputs and outputs are pluggable, the connection is made using pre-assembled cables. An optional cover inside provides the necessary protection against accidental contact.


  • Bildtitel

    4-fach Triacmodul

    Button
  • Bildtitel

    4-fach Triacmodul

    Button

Technical data (excerpt)


Rated power: 16 AACeff , 3680W

Triac:                                        40A, Typ BTA 41-800BRG

Switching behavior: zero voltage switch

Rated operating voltage: 400 VACrms

Operating voltage range: 24...480 VACrms

Peak blocking voltage: 800 Vp

Frequency range: 45...65 Hz

Control voltage: 5...30 VDC / 10...15mA, positive and negative switching

Input resistance: 1.0 k

Temperature range: operation –5... 50 °C

Storage –40... 70°C

Protection class: IP 54

Maße (H x B x T):                    99,5 x 250,0 x 98,0 mm


Variants for controlling the controller


Depending on local conditions, the cables can be fed in from the left or right.


A maximum of 8 zones can be connected via a DC control line.